جدول المواصفات لـ RMXS-EV

RMXS112E8V1B RMXS140E8V1B RMXS160E8V1B
Sound pressure level Heating Nom. dBA 53 54 55
  Cooling Nom. dBA 51 52 54
  Night quiet mode Level 3 dBA 41.0 41.0 41.0
Standard Accessories أنبوب توصيل الغاز 3 3 3
  Installation manual 1 1 1
  Operation manual 1 1 1
  تجويف المصرف 1 1 1
  غطاء المصرف 2 2 2
  مستقبل الصرف 3 3 3
  العازل 1 1 1
Maximum number of connectable indoor units (BP to be connected) 6 8 9
Refrigerant النوع   R-410A R-410A R-410A
Indoor index connection Min.   55 70 80
  Max.   145.5 182 208
Cooling capacity Nom. kW 11.2 (1) 14.0 (1) 15.5 (1)
Piping connections Liquid القطر الخارجي mm 9.52 9.52 9.52
    النوع   Flare connection Flare connection Flare connection
  غاز القطر الخارجي mm 19.1 19.1 19.1
    النوع   Braze connection Braze connection Braze connection
  Drain OD mm 26x3 26x3 26x3
    Type   Hole Hole Hole
  Level difference IU - IU Max. م 15 15 15
    OU - IU م 30 30 30
    IU - OU Max. م 30 30 30
  Additional refrigerant charge kg/m See installation manual See installation manual See installation manual
  طول الأنابيب الإجمالي النظام فعلي م 115 135 145
Sound power level Cooling Nom. dBA 67 68 70
COP 3.18 3.07 3.22
Compressor Type   Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Dimensions Unit العرض mm 900 900 900
    العمق mm 320 320 320
    الارتفاع mm 1,345 1,345 1,345
الوزن الوحدة kg 120 120 120
EER 3.20 2.75 2.87
Heating capacity Nom. kW 12.5 (2) 16.0 (2) 17.5 (2)
Power supply الطور   1N~ 1N~ 1N~
  Frequency Hz 50 50 50
  Voltage V 220-240 220-240 220-240
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m; level difference: 0m. (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m; level difference: 0m.
  (2) - Heating: indoor temp. 20°CDB, outdoor temp. 7°CDB, 6°CWB, equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m / level difference: 0m. (2) - Heating: indoor temp. 20°CDB, outdoor temp. 7°CDB, 6°CWB, equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m / level difference: 0m. (2) - Heating: indoor temp. 20°CDB, outdoor temp. 7°CDB, 6°CWB, equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m / level difference: 0m.
  (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates.
  (4) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (4) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (4) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (5) - Sound levels are measured in an anechoic room. (5) - Sound levels are measured in an anechoic room. (5) - Sound levels are measured in an anechoic room.
  (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (6) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%.
  (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA
  (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker
  (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (11) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (12) - MSC means the maximum current during start up of the compressor (12) - MSC means the maximum current during start up of the compressor (12) - MSC means the maximum current during start up of the compressor
  (13) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (13) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (13) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase.
  (14) - Ssc: Short-circuit power (14) - Ssc: Short-circuit power (14) - Ssc: Short-circuit power
  (15) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase (15) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase (15) - Minimum Ssc value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase